Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
Measuring range |
|
Communication interface |
IO-Link |
Process connection |
threaded connection G 1/2 external thread |
Installation length EL |
150 |
Special feature |
Gold-plated contacts |
Measuring element |
1 x Pt 1000; (to DIN EN 60751, class A) |
Media |
liquids and gases |
Pressure rating |
|
Operating voltage |
18...32 DC; ("supply class 2" to cULus) |
Current consumption |
< 50 |
Protection class |
III |
Reverse polarity protection |
yes |
Power-on delay time |
1 |
Integrated watchdog |
yes |
Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
Total number of outputs |
2 |
Output signal |
switching signal; analogue signal; IO-Link; (configurable) |
Electrical design |
PNP/NPN |
Number of digital outputs |
2 |
Output function |
normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC |
2.5 |
Permanent current rating of switching output DC |
250 |
Number of analogue outputs |
1 |
Analogue current output |
4...20 |
Max. load |
500 |
Analogue voltage output |
0...10 |
Min. load resistance |
2000 |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Overload protection |
yes |
Probe length L |
133.2 |
Measuring range |
|
Factory setting |
-50...150 °C |
Set point SP |
-49.8...150 °C | -57.6...302 °F |
|
Reset point rP |
-50...149.8 °C | -58...301.6 °F |
|
Analogue start point |
|
Analogue end point |
|
In steps of |
|
Resolution |
|
Resolution of switching output |
0.1 |
Resolution of analogue output |
current output: MS / 4096; voltage output: MS / 3561 |
Resolution of display |
0.1 |
Switch point accuracy |
± 0,3 + (± 0,1 % MS) |
Precision analogue output |
± 0,3 + (± 0,1 % MS) |
Display accuracy |
± 0,3 + (± 0,1 % MS) |
Temperature coefficient |
0,1; (in case of deviation from the reference condition 25 ± 5 °C) |
Dynamic response T05 / T09 |
1 / 3; (to DIN EN 60751) |
Parameter setting options |
hysteresis / window; normally open / normally closed; switching logic; switch-on/switch-off delay; Damping; Display unit; current/voltage output |
Communication interface |
IO-Link |
Transmission type |
COM2 (38,4 kBaud) |
IO-Link revision |
1.1 |
Ambient temperature |
-25...80 |
Storage temperature |
-40...100 |
Protection |
IP 67 |
EMC |
DIN EN 61000-6-2 | | DIN EN 61000-6-3 | |
|
Shock resistance |
DIN IEC 68-2-27 | 50 g (11 ms) |
|
Vibration resistance |
DIN EN 60068-2-6 | 20 g (10...2000 Hz) |
|
MTTF |
207 |
UL approval |
|
Weight |
311 |
Housing |
cylindrical |
Dimensions |
Ø 34 / L = 237 |
Materials |
stainless steel (316L/1.4404); PBT+PC-GF30; PBT-GF20; PC |
Materials (wetted parts) |
stainless steel (316L/1.4404); O-ring: FKM |
Tightening torque |
45 |
Process connection |
threaded connection G 1/2 external thread |
Probe diameter |
6 |
Installation length EL |
150 |
Display |
Display unit | 2 x LED, green | switching status | 2 x LED, yellow | measured values | alphanumeric display, red/green 4-digit |
|
Remarks |
MS = set measuring span | The values for accuracy apply to flowing water. |
|
Pack quantity |
1 pcs. |
Connection |
Connector: 1 x M12; coding: A; Contacts: gold-plated |