« Back
PN7299 - Pressure sensor with display

PN7299 - Pressure sensor with display

PRODUCENT CODE: PN7299
CATEGORY: Type PN / PE with digital display
Producer: ifm electronic
1594.13 PLN
(net)
1 working day
5 pcs in stock
Stock levels are indicative. If the ordered goods are not in stock, we will inform you about the current delivery date.
Fast shipping
Shipping cost: 20 PLN
Do you have questions about the product?
Ask an experienced consultant:
+48 32 237 61 98 w. 101
bn@newtech.com.pl
Description
PN-1-1BREN14-QFRKG/US/ /V
  • Two switching outputs, one of them with IO-Link communication interface
  • Red/green display for clear identification of the acceptable range
  • The process connection can be rotated for optimum alignment
  • With long-term stability thanks to high overload protection
  • Robust design for use in harsh industrial environments
Technical data
Product characteristics
Number of inputs and outputs Number of digital outputs: 2
Measuring range
-1...1 bar-1000...1000 mbar-14.5...14.5 psi-29.4...29.4 inHg-100...100 kPa
Process connection threaded connection 1/4" NPT internal thread
Application
Special feature Gold-plated contacts
Measuring element ceramic-capacitive pressure measuring cell
Application for industrial applications
Media liquids and gases
Medium temperature -25...80
Min. bursting pressure
30000 mbar450 psi880 inHg3000 kPa
Pressure rating
10000 mbar145 psi290 inHg1000 kPa
Type of pressure relative pressure; vacuum
MAWP (for applications according to CRN)
20 bar20000 mbar290 psi590.59 inHg2000 kPa
Electrical data
Operating voltage 18...30 DC; (to SELV/PELV)
Current consumption < 35
Min. insulation resistance 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Power-on delay time < 0.3
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2
Outputs
Total number of outputs 2
Output signal switching signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC 2.5
Permanent current rating of switching output DC 150; (200 (...60 °C) 250 (...40 °C))
Switching frequency DC < 170
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Measuring range
-1...1 bar-1000...1000 mbar-14.5...14.5 psi-29.4...29.4 inHg-100...100 kPa
Factory setting / CMPT = 2
Set point SP
-980...1000 mbar-14.3...14.5 psi-29...29.6 inHg-98...100 kPa
Reset point rP
-990...990 mbar-14.4...14.4 psi-29.4...29.2 inHg-99...99 kPa
Min. difference between SP and rP
10 mbar0.2 psi0.4 inHg1 kPa
In steps of
10 mbar0.1 psi0.2 inHg1 kPa
Status_B High Resolution / CMPT = 3
Set point SP
-983...1000 mbar-14.3...14.5 psi-29...29.5 inHg-98...100 kPa
Reset point rP
-993...990 mbar-14.4...14.4 psi-29.3...29.2 inHg-99...99 kPa
Min. difference between SP and rP
10 mbar0.2 psi0.3 inHg1 kPa
In steps of
1 mbar0.1 psi0.1 inHg1 kPa
Accuracy / deviations
Switch point accuracy < ± 0,5
Repeatability < ± 0,1; (with temperature fluctuations < 10 K)
Characteristics deviation < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation < ± 0,25
Long-term stability < ± 0,05; (per 6 months)
Temperature coefficient zero point < ± 0,2; (-0...80 °C)
Temperature coefficient span < ± 0,2; (-0...80 °C)
Response times
Response time < 3
Delay time programmable dS, dr 0...50
Software / programming
Parameter setting options hysteresis / window; normally open / normally closed; switching logic; switch-on/switch-off delay; Damping; Display unit
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
SIO mode yes
Required master port type A; (when pin 2 not connected: B)
Supported DeviceIDs
Type of operationDeviceID
Factory setting / CMPT = 2457
Status_B High Resolution / CMPT = 3636
Note
For further information please see the IODD PDF file under "Downloads"
Factory setting / CMPT = 2
Profiles Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
Min. process cycle time 2.3
IO-Link resolution pressure
1 mbar0.001 MPa
IO-Link process data (cyclical)
functionbit length
pressure14
binary switching information2
IO-Link functions (acyclical) application specific tag
Status_B High Resolution / CMPT = 3
Profiles Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000)
Min. process cycle time 3
IO-Link resolution pressure
1 mbar0.001 MPa
IO-Link process data (cyclical)
functionbit length
pressure16
device status4
binary switching information2
IO-Link functions (acyclical) application specific tag
Operating conditions
Ambient temperature -25...80
Storage temperature -40...100
Protection IP 65; IP 67
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance
DIN EN 60068-2-2750 g (11 ms)
Vibration resistance
DIN EN 60068-2-620 g (10...2000 Hz)
MTTF 260
UL approval
UL Approval no.J001
Pressure Equipment Directive Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight 221.5
Housing cylindrical
Dimensions Ø 34 / L = 90.7
Materials stainless steel (316L/1.4404); PBT+PC-GF30; PBT-GF20; PC
Materials (wetted parts) stainless steel (316L/1.4404); ceramics; FKM
Min. pressure cycles 100 million
Tightening torque 2...3 turns after hand-fastening; recommended tightening torque; depends on lubrication, seal and pressure rating
Process connection threaded connection 1/4" NPT internal thread
Restrictor element integrated no (can be retrofitted)
Displays / operating elements
Display
Display unit4 x LED, green (bar, psi, kPa, inHg)
switching status2 x LED, yellow
measured valuesalphanumeric display, red/green 4-digit
Remarks
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; coding: A; Contacts: gold-plated