« Back
PN7094 - Pressure sensor with display

PN7094 - Pressure sensor with display

PRODUCENT CODE: PN7094
CATEGORY: Type PN / PE with digital display
Producer: ifm electronic
1529.10 PLN
(net)
1 working day
1 pcs in stock
Stock levels are indicative. If the ordered goods are not in stock, we will inform you about the current delivery date.
Fast shipping
Shipping cost: 20 PLN
Do you have questions about the product?
Ask an experienced consultant:
+48 32 237 61 98 w. 101
bn@newtech.com.pl
Description
PN-010-RER14-QFRKG/US/ /V
  • Two switching outputs, one of them with IO-Link communication interface
  • Red/green display for clear identification of the acceptable range
  • The process connection can be rotated for optimum alignment
  • With long-term stability thanks to high overload protection
  • Robust design for use in harsh industrial environments
Technical data
Product characteristics
Number of inputs and outputs Number of digital outputs: 2
Measuring range
-1...10 bar-14.5...145 psi-0.1...1 MPa
Process connection threaded connection G 1/4 internal thread
Application
Special feature Gold-plated contacts
Measuring element ceramic-capacitive pressure measuring cell
Application for industrial applications
Media liquids and gases
Medium temperature -25...80
Min. bursting pressure
150 bar2175 psi15 MPa
Pressure rating
75 bar1087 psi7.5 MPa
Vacuum resistance
-1000 mbar-0.1 MPa
Type of pressure relative pressure; vacuum
Electrical data
Operating voltage 18...30 DC; (to SELV/PELV)
Current consumption < 35
Min. insulation resistance 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Power-on delay time < 0.3
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2
Outputs
Total number of outputs 2
Output signal switching signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC 2.5
Permanent current rating of switching output DC 150; (200 (...60 °C) 250 (...40 °C))
Switching frequency DC < 170
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Measuring range
-1...10 bar-14.5...145 psi-0.1...1 MPa
Factory setting / CMPT = 2
Set point SP
-0.9...10 bar-13.5...145 psi-0.09...1 MPa
Reset point rP
-0.95...9.95 bar-14...144.5 psi-0.095...0.995 MPa
Min. difference between SP and rP
0.05 bar1 psi0.005 MPa
In steps of
0.05 bar0.5 psi0.005 MPa
Status_B High Resolution / CMPT = 3
Set point SP
-0.92...10 bar-13.3...145 psi-0.092...1 MPa
Reset point rP
-0.97...9.95 bar-14...144.3 psi-0.097...0.995 MPa
Min. difference between SP and rP
0.05 bar0.8 psi0.005 MPa
In steps of
0.01 bar0.1 psi0.001 MPa
Accuracy / deviations
Switch point accuracy < ± 0,5
Repeatability < ± 0,1; (with temperature fluctuations < 10 K)
Characteristics deviation < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation < ± 0,25
Long-term stability < ± 0,05; (per 6 months)
Temperature coefficient zero point < ± 0,2; (0...80 °C)
Temperature coefficient span < ± 0,2; (0...80 °C)
Response times
Response time < 3
Delay time programmable dS, dr 0...50
Software / programming
Parameter setting options hysteresis / window; normally open / normally closed; switching logic; switch-on/switch-off delay; Damping; Display unit
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
SIO mode yes
Required master port type A; (when pin 2 not connected: B)
Supported DeviceIDs
Type of operationDeviceID
Factory setting / CMPT = 2403
PN7004311
Status_B High Resolution / CMPT = 3601
Note
For further information please see the IODD PDF file under "Downloads"
Factory setting / CMPT = 2
Profiles Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
Min. process cycle time 2.3
IO-Link resolution pressure
0.01 bar0.001 MPa
IO-Link process data (cyclical)
functionbit length
pressure14
binary switching information2
IO-Link functions (acyclical) application specific tag
Status_B High Resolution / CMPT = 3
Profiles Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000)
Min. process cycle time 3
IO-Link resolution pressure
0.005 bar0.0005 MPa
IO-Link process data (cyclical)
functionbit length
pressure16
device status4
binary switching information2
IO-Link functions (acyclical) application specific tag
Operating conditions
Ambient temperature -25...80
Storage temperature -40...100
Protection IP 65; IP 67
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance
DIN EN 60068-2-2750 g (11 ms)
Vibration resistance
DIN EN 60068-2-620 g (10...2000 Hz)
MTTF 260
UL approval
UL Approval no.J001
Pressure Equipment Directive Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight 241.7
Housing cylindrical
Dimensions Ø 34 / L = 90.7
Materials stainless steel (316L/1.4404); PBT+PC-GF30; PBT-GF20; PC
Materials (wetted parts) stainless steel (316L/1.4404); ceramics; FKM
Min. pressure cycles 100 million
Tightening torque 25...35; (recommended tightening torque; depends on lubrication, seal and pressure rating)
Process connection threaded connection G 1/4 internal thread
Displays / operating elements
Display
Display unit3 x LED, green (bar, psi, MPa)
switching status2 x LED, yellow
measured valuesalphanumeric display, red/green 4-digit
Remarks
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; coding: A; Contacts: gold-plated