« Back
PN2599 - Pressure sensor with display

PN2599 - Pressure sensor with display

PRODUCENT CODE: PN2599
CATEGORY: Type PN / PE with digital display
Producer: ifm electronic
1941.84 PLN
(net)
1 working day
2 pcs in stock
Stock levels are indicative. If the ordered goods are not in stock, we will inform you about the current delivery date.
Fast shipping
Shipping cost: 20 PLN
Do you have questions about the product?
Ask an experienced consultant:
+48 32 237 61 98 w. 101
bn@newtech.com.pl
Description
PN-1-1BREG14-MFRKG/US/ /V
  • Two switching outputs, one of them programmable as IO-Link and one as analogue output
  • Red/green display for clear identification of the acceptable range
  • The process connection can be rotated for optimum alignment
  • With long-term stability thanks to high overload protection
  • Robust design for use in harsh industrial environments
Technical data
Product characteristics
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Measuring range
-1...1 bar-1000...1000 mbar-14.5...14.5 psi-29.5...29.5 inHg-401...401 inH2O-100...100 kPa
Process connection threaded connection G 1/4 external thread (DIN EN ISO 1179-2); internal thread:M5
Application
Special feature Gold-plated contacts
Measuring element ceramic-capacitive pressure measuring cell
Application for industrial applications
Media liquids and gases
Medium temperature -25...80
Min. bursting pressure
30000 mbar450 psi3000 kPa
Pressure rating
10000 mbar145 psi1000 kPa
Vacuum resistance
-1000 mbar-0.1 MPa
Type of pressure relative pressure; vacuum
Electrical data
Operating voltage 18...30 DC; (to SELV/PELV)
Current consumption < 35
Min. insulation resistance 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Power-on delay time 0.3
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Outputs
Total number of outputs 2
Output signal switching signal; analogue signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC 2
Permanent current rating of switching output DC 250
Switching frequency DC < 500
Number of analogue outputs 1
Analogue current output 4...20; (scalable 1:5)
Max. load 500
Analogue voltage output 0...10; (scalable 1:5)
Min. load resistance 2000
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Measuring range
-1...1 bar-1000...1000 mbar-14.5...14.5 psi-29.5...29.5 inHg-401...401 inH2O-100...100 kPa
Analogue start point
-1000...600 mbar-14.5...8.7 psi-29.5...17.7 inHg-402...240 inH2O-100...60 kPa
Analogue end point
-600...1000 mbar-8.7...14.5 psi-17.7...29.5 inHg-240...402 inH2O-60...100 kPa
Factory setting / CMPT = 2
Set point SP
-985...1000 mbar-14.3...14.5 psi-29.2...29.5 inHg-396...402 inH2O-98.5...100 kPa
Reset point rP
-995...990 mbar-14.45...14.4 psi-29.4...29.3 inHg-400...398 inH2O-99.5...99 kPa
Min. difference between SP and rP
10 mbar0.15 psi0.3 inHg4 inH2O1 kPa
In steps of
5 mbar0.05 psi0.1 inHg2 inH2O0.5 kPa
Status_B High Resolution / CMPT = 3
Set point SP
-987...1000 mbar-14.32...14.5 psi-29.2...29.5 inHg-396...401 inH2O-98.7...100 kPa
Reset point rP
-996...992 mbar-14.44...14.38 psi-29.4...29.3 inHg-400...398 inH2O-99.6...99.2 kPa
Min. difference between SP and rP
9 mbar0.12 psi0.3 inHg4 inH2O0.9 kPa
In steps of
1 mbar0.01 psi0.1 inHg1 inH2O0.1 kPa
Accuracy / deviations
Switch point accuracy < ± 0,4; (Turn down 1:1)
Repeatability < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1)
Characteristics deviation < ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation < ± 0,1; (Turn down 1:1)
Long-term stability < ± 0,05; (Turn down 1:1; per 6 months)
Temperature coefficient zero point < ± 0,2; (-0...80 °C)
Temperature coefficient span < ± 0,2; (-0...80 °C)
Notes on the accuracy / deviation switch point accuracy, linearity error under DNV GL: < ± 1%: < ± 1%
Response times
Response time < 1.5
Delay time programmable dS, dr 0...50
Damping process value dAP 0...4
Damping for the analogue output dAA 0...4
Max. response time analogue output 3
Software / programming
Parameter setting options hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
SIO mode yes
Required master port type A; (when pin 2 not connected: B)
Supported DeviceIDs
Type of operationDeviceID
Factory setting / CMPT = 2467
Status_B High Resolution / CMPT = 3983
Note
For further information please see the IODD PDF file under "Downloads"
Factory setting / CMPT = 2
Profiles Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
Min. process cycle time 2.3
IO-Link resolution pressure 1
IO-Link process data (cyclical)
functionbit length
pressure14
binary switching information2
IO-Link functions (acyclical) application specific tag
Status_B High Resolution / CMPT = 3
Profiles Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000)
Min. process cycle time 3
IO-Link resolution pressure 1
IO-Link process data (cyclical)
functionbit length
pressure16
device status4
binary switching information2
IO-Link functions (acyclical) application specific tag
Operating conditions
Ambient temperature -25...80
Storage temperature -40...100
Protection IP 65; IP 67
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance
DIN EN 60068-2-2750 g (11 ms)
Vibration resistance
DIN EN 60068-2-620 g (10...2000 Hz)
MTTF 138
UL approval
UL Approval no.J012
Pressure Equipment Directive Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight 264.5
Housing cylindrical
Dimensions Ø 34 / L = 92.7
Materials stainless steel (316L/1.4404); PBT+PC-GF30; PBT-GF20; PC
Materials (wetted parts) stainless steel (316L/1.4404); Al2O3 (ceramics); FKM
Min. pressure cycles 100 million
Tightening torque 25...35; (recommended tightening torque; depends on lubrication, seal and pressure rating)
Process connection threaded connection G 1/4 external thread (DIN EN ISO 1179-2); internal thread:M5
Process connection sealing FKM (DIN EN ISO 1179-2)
Restrictor element integrated no (can be retrofitted)
Displays / operating elements
Display
Display unit5 x LED, green (mbar, psi, kPa, inH2O, inHg)
switching status2 x LED, yellow
measured valuesalphanumeric display, red/green 4-digit
Remarks
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; coding: A; Contacts: gold-plated