| Number of inputs and outputs |
Number of digital outputs: 1; Number of analogue outputs: 1 |
| Measuring range |
| -1...10 bar | -14.4...145 psi |
|
| Process connection |
threaded connection G 1/2 external thread |
| Special feature |
Gold-plated contacts |
| Application |
for industrial applications |
| Media |
liquids and gases |
| Medium temperature |
-25...80 |
| Min. bursting pressure |
|
| Pressure rating |
|
| Type of pressure |
relative pressure; vacuum |
| MAWP (for applications according to CRN) |
|
| Operating voltage |
18...32 DC |
| Current consumption |
< 70; (24 V) |
| Min. insulation resistance |
100; (500 V DC) |
| Protection class |
III |
| Reverse polarity protection |
yes |
| Power-on delay time |
6 |
| Integrated watchdog |
yes |
| Number of inputs and outputs |
Number of digital outputs: 1; Number of analogue outputs: 1 |
| Total number of outputs |
2 |
| Output signal |
switching signal; analogue signal; (configurable) |
| Electrical design |
PNP/NPN |
| Number of digital outputs |
1 |
| Output function |
normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC |
2 |
| Permanent current rating of switching output DC |
250 |
| Switching frequency DC |
75 |
| Number of analogue outputs |
1 |
| Analogue current output |
4...20, invertible; (scalable) |
| Max. load |
(Ub - 10 V) / 20 mA |
| Short-circuit protection |
yes |
| Type of short-circuit protection |
pulsed |
| Overload protection |
yes |
| Measuring range |
| -1...10 bar | -14.4...145 psi |
|
| Set point SP |
| -0.96...16 bar | -14...232 psi |
|
| Reset point rP |
| -1...15.96 bar | -14.4...231.6 psi |
|
| Analogue start point |
| -1...13.5 bar | -14.4...195.8 psi |
|
| Analogue end point |
| 1.5...16 bar | 21.8...232 psi |
|
| In steps of |
|
| Switch point accuracy |
< ± 0,5; (Turn down 1:1) |
| Repeatability |
< ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
| Characteristics deviation |
< ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line) |
| Hysteresis deviation |
< ± 0,25; (Turn down 1:1) |
| Long-term stability |
< ± 0,1; (Turn down 1:1; per 6 months) |
| Temperature coefficient zero point |
< ± 0,2; (0...70 °C) |
| Temperature coefficient span |
< ± 0,2; (0...70 °C) |
| Response time |
< 9 |
| Damping process value dAP |
0.01...30 |
| Damping for the analogue output dAA |
0.01...30 |
| Step response time analogue output |
28 |
| Ambient temperature |
-20...80 |
| Storage temperature |
-40...100 |
| Protection |
IP 67; IP 69K |
| EMC |
| DIN EN 61000-6-2 | | | DIN EN 61000-6-3 | |
|
| Shock resistance |
| DIN EN 60068-2-27 | 50 g (11 ms) |
|
| Vibration resistance |
| DIN EN 60068-2-6 | 10 g (10...2000 Hz) |
|
| MTTF |
103 |
| Pressure Equipment Directive |
Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| Weight |
565.1 |
| Dimensions |
169 x 100 x 57 |
| Materials |
stainless steel (316L/1.4404); PA; FKM; PTFE; viewing glass: laminated safety glass 4 mm |
| Materials (wetted parts) |
Al2O3 (ceramics); FKM; stainless steel (316L/1.4404) |
| Min. pressure cycles |
100 million |
| Process connection |
threaded connection G 1/2 external thread |
| Restrictor element integrated |
no (can be retrofitted) |
| Display |
| Display unit | 2 x LED, green | | switching status | LED, yellow | | switch points | LED ring, red | | function display | alphanumeric display, red 4-digit | | measured values | analogue display, 0...350° rotatable, pointer not visible when unit disconnected | | measured values | alphanumeric display, red 4-digit |
|
| With scale |
yes |
| Extended display range (max.) |
|
| Remarks |
| switch point accuracy in the extended display range: 1.5 % of the span |
|
| Pack quantity |
1 pcs. |
| Connection |
Connector: 1 x M12; coding: A; Contacts: gold-plated |