« Back
PE2094 - Pressure sensor with display

PE2094 - Pressure sensor with display

PRODUCENT CODE: PE2094
CATEGORY: Type PN / PE with digital display
Producer: ifm electronic
1862.64 PLN
(net)
1 working day
1 pcs in stock
Stock levels are indicative. If the ordered goods are not in stock, we will inform you about the current delivery date.
Fast shipping
Shipping cost: 20 PLN
Do you have questions about the product?
Ask an experienced consultant:
+48 32 237 61 98 w. 101
bn@newtech.com.pl
Description
PE-010-RER14-MFRKG/US/ /E
  • Two switching outputs, one of them programmable as IO-Link and one as analogue output
  • Red/green display for clear identification of the acceptable range
  • The process connection can be rotated for optimum alignment
  • With long-term stability thanks to high overload protection
  • Robust design for use in harsh industrial environments
Technical data
Product characteristics
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Measuring range
-1...10 bar-14.6...145 psi-0.1...1 MPa
Process connection threaded connection G 1/4 internal thread
Application
Special feature Gold-plated contacts
Measuring element ceramic-capacitive pressure measuring cell
Application for industrial applications
Media liquids and gases
Medium temperature -25...80
Min. bursting pressure
150 bar2175 psi15 MPa
Pressure rating
75 bar1087 psi7.5 MPa
Vacuum resistance
-1000 mbar-0.1 MPa
Type of pressure relative pressure
Electrical data
Operating voltage 18...30 DC; (to SELV/PELV)
Current consumption < 35
Min. insulation resistance 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Power-on delay time 0.3
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Outputs
Total number of outputs 2
Output signal switching signal; analogue signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC 2
Permanent current rating of switching output DC 250
Switching frequency DC < 500
Number of analogue outputs 1
Analogue current output 4...20; (scalable 1:5)
Max. load 500
Analogue voltage output 0...10; (scalable 1:5)
Min. load resistance 2000
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Measuring range
-1...10 bar-14.6...145 psi-0.1...1 MPa
Set point SP
-0.94...10 bar-13.6...145 psi-0.094...1 MPa
Reset point rP
-0.98...9.96 bar-14.2...144.4 psi-0.098...0.996 MPa
Analogue start point
-1...8 bar-14.6...116 psi-0.1...0.8 MPa
Analogue end point
1...10 bar14.6...145 psi0.1...1 MPa
In steps of
0.02 bar0.2 psi0.002 MPa
Accuracy / deviations
Switch point accuracy < ± 0,4; (Turn down 1:1)
Repeatability < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1)
Characteristics deviation < ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation < ± 0,1; (Turn down 1:1)
Long-term stability < ± 0,05; (Turn down 1:1; per 6 months)
Temperature coefficient zero point 0,2; (-25...80 °C)
Temperature coefficient span 0,2; (-25...80 °C)
Notes on the accuracy / deviation switch point accuracy, linearity error under DNV GL: < ± 1%: < ± 1%
Response times
Response time < 1.5
Delay time programmable dS, dr 0...50
Damping process value dAP 0...4
Damping for the analogue output dAA 0...4
Max. response time analogue output 3
Software / programming
Parameter setting options hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
Profiles Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO mode yes
Required master port type A
Process data analogue 1
Process data binary 2
Min. process cycle time 2.3
Supported DeviceIDs
Type of operationDeviceID
default463
Operating conditions
Ambient temperature -25...80
Storage temperature -40...100
Protection IP 65; IP 67
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance
DIN EN 60068-2-2750 g (11 ms)
Vibration resistance
DIN EN 60068-2-620 g (10...2000 Hz)
MTTF 161
UL approval
UL Approval no.J012
Pressure Equipment Directive Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight 236.5
Housing cylindrical
Dimensions Ø 34 / L = 90.7
Materials stainless steel (316L/1.4404); PBT+PC-GF30; PBT-GF20; PC
Materials (wetted parts) stainless steel (316L/1.4404); Al2O3 (99.9%; ceramics); EPDM
Min. pressure cycles 100 million
Tightening torque 25...35; (recommended tightening torque; depends on lubrication, seal and pressure rating)
Process connection threaded connection G 1/4 internal thread
Restrictor element integrated no (can be retrofitted)
Displays / operating elements
Display
Display unit3 x LED, green (bar, psi, MPa)
switching status2 x LED, yellow
measured valuesalphanumeric display, red/green 4-digit
Remarks
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; coding: A; Contacts: gold-plated